NEC Ampacity Charts

Ampacity is the maximum current that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. Current is measured in amps. You must use the correct size wire for the current (load) requirement of the circuit to prevent the wire from overheating.

Wire Gauge Size
Copper Aluminum
60˚ C
(140˚) F
75˚ C
(167˚) F
90˚ C
(194˚) F
75˚ C
(167˚) F
90˚ C
(194˚) F
NM-B THW THWN-2 THW XHHW-2
UF-B THWN THHN THWN THHN
SE XHHW-2 SE TWHN-2
USE USE
XHHW XHHW
14 15 20 25
12 20 25 30 20 25
10 30 35 40 30 35
8 40 50 55 40 45
6 55 65 75 50 55
4 70 85 95 65 75
3 85 100 115 75 85
2 95 115 130 90 100
1 130 145 100 115
1/0 150 170 120 135
2/0 175 195 135 150
3/0 200 225 155 175
4/0 230 260 180 205
250 255 290 205 230
300 285 320 230 260
350 310 350 250 280
500 380 430 310 350
600 420 475 340 385
750 475 535 385 435
1000 545 615 445 500